ข้อมูลสินค้า
- 16- to 328-foot protection range
- Single-ended, reflective design
- User-friendly alignment procedure
- Six user selectable sensitivity levels
- Optional integral NFPA 72 sensitivity test feature
- Removable plug-in terminal blocks
- Digital display for easy alignment
- Built-in automatic gain control compensates for signal deterioration from dust build-up
- Remote test station option
- Paintable cover
- Easiest alignment in the industry
- Heater kits for transmitter/receiver and reflector option
Operational Speci cations | |
Protection Range | 16 ft. to 328 ft. (5m to 100m) |
Adjustment Angle | +/– 10 Degrees horizontal & vertical (The optics move independent of the unit) |
Sensitivity Levels | Level 1 – 25% Level 2 – 30% Level 3 – 40% Level 4 – 50% Acclimate Level 1 – 30–50% Acclimate Level 2 – 40–50% |
Fault Condition (Trouble) | 96% or more obscuration blockage
In alignment mode |
Alignment Aid | Optical gunsight
Integral signal strength indication |
Alarm Indicator | Local red LED and remote alarm |
Trouble Indicator | Local yellow LED and remote trouble |
Normal Indicator | Local flashing green LED |
Test/Reset Features | Integral Sensitivity Test Filter (BEAM1224S only) Sensitivity filter (Incremental scale on reflector) Local alarm test switch
Local alarm reset switch |
Smoke Detector Spacing | On smooth ceilings, 30–60 feet between projected beams and not more than one-half that spacing between a projected beam and a sidewall. Other spacing may be used depending on ceiling height, airflow characteristics, and response requirements. See NFPA 72. |
Electrical Speci cations (BEAMHKR) | |
Voltage | 15 to 32V |
Current | 450mA Max at 32V (per reflector) |
Power Consumption | 7.7W @24V; 15W @ 32V (per reflector) |